Huawei UPS5000-E Series User Manual page 63

50 kva power modules
Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Item
Mains
Mains input current (A)
input
Recommended
cross-sectional
2
area (mm
)
Bypass
Bypass input current
input
(A)
Recommended
cross-sectional
2
area (mm
)
Output
Output current (A)
Recommended
cross-sectional
2
area (mm
)
Battery
Battery nominal
input
discharge current (A)
Battery maximum
discharge current (A)
Recommended
cross-sectional
2
area (mm
)
Issue 11 (2019-12-20)
UPS5000-E-200K-SM/FM
50 kVA
89
L1
4 x 25
L2
L3
N
PE
25
76
L1
4 x 25
L2
L3
N
PE
25
76
U
4 x 25
V
W
N
PE
25
110
131
+
3 x 35
N
-
PE
35
When selecting, connecting, and routing power cables, follow local safety regulations
and rules.
Copyright © Huawei Technologies Co., Ltd.
100 kVA
150 kVA
178
267
2 x (4 x
4 x 70
70)
35
70
152
228
4 x 70
2 x (4 x
70)
35
70
152
228
4 x 70
2 x (4 x
70)
35
70
219
329
263
394
3 x 95
2 x (3 x
95)
50
95
UPS5000-E-300K-SM
/SMT
200 kVA
250 kVA
355
444
2 x (4 x
2 x (4 x
95)
120)
95
120
304
380
2 x (4 x
2 x (4 x
95)
120)
95
120
304
380
2 x (4 x
2 x (4 x
95)
120)
95
120
439
548
525
657
2 x (3 x
2 x (3 x
120)
150)
120
150
3 Installation
300 kVA
533
2 x (4 x
150)
150
456
2 x (4 x
150)
150
456
2 x (4 x
150)
150
658
788
2 x (3 x
185)
185
53