Huawei UPS5000-E Series User Manual page 205

50 kva power modules
Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Item
Inverter async.
alarm
Bus
overvoltage
recovery
Bus overvolt.
recovery time
Capacitor
failure
detection
Issue 11 (2019-12-20)
Description
Specifies whether an Inverter
asynchronous alarm can be
displayed on the LCD when the
inverter cannot track the bypass
frequency change. Normal power
supply is not affected no matter
whether this parameter is set to
Enable or Disable.
Specifies whether to
automatically clear the alarm and
restart the power module when
the rectifier or inverter shuts
down due to a bus overvoltage
alarm. If Bus overvoltage
recovery is set to Enable, the
bus overvoltage alarm is
automatically cleared, and the
rectifier and inverter
automatically start when the bus
voltage recovers (less than 420
V) within Bus overvolt.
recovery time. When Bus
overvoltage recovery is set to
Disable, the bus overvoltage
alarm cannot be automatically
cleared, and the rectifier and
inverter cannot automatically
start.
If Bus overvoltage recovery is
set to Enable, the bus
overvoltage alarm is
automatically cleared, and the
rectifier and inverter
automatically start when the bus
voltage recovers (less than 420
V) within Bus overvolt.
recovery time.
If Capacitor failure detection is
set to Enable, the power module
(power unit) performs inverter
capacitor fault detection based on
the settings of Capacitor failure
detection upper limit and
Capacitor failure detection
lower limit. If the power module
determines that the inverter
capacitor is faulty, it shuts down
the inverter to prevent the fault
from expanding.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Disable
Disable, Enable
Enable
Disable, Enable
5s
5s, 1 min, 5 min,
10 min
Disable
Disable, Enable
195

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents