Huawei UPS5000-E Series User Manual page 268

50 kva power modules
Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Alarm ID
Alarm Name
(Alarm
ID-Cause
ID)
0004-1
Mains ph. Reversed
0005-1
Mains neutral
absent
0006-1
Mains undervoltage
0010-1
Abnormal bypass
voltage
0010-2
0011-1
Bypass phase
reversed
0012-1
Bypass neutral
absent
Battery connected
0020-1
reversely
Issue 11 (2019-12-20)
Severity
Cause
Minor
Cable connections
are incorrect.
Minor
Cable connections
are incorrect.
Minor
The mains is not
normal.
The power
module sampling
circuit is not
normal.
Minor
The bypass
voltage range is
not correctly set.
The bypass input
voltage is not
normal.
The bypass
frequency range
is not correctly
set.
The bypass input
frequency is not
normal.
Minor
The phase sequence
of the three-phase
bypass input is
reversed.
Minor
The neutral wire of
bypass input is not
installed properly.
Batteries are not
Critical
properly installed.
Copyright © Huawei Technologies Co., Ltd.
B Alarm List
Solution
Verify the cable connections.
1. Secure or connect the neutral
wire to the cabinet if it is loose
or disconnected.
2. Check that the neutral wire to
the power distribution system
is normal.
Check whether the mains voltage
ranges from 80 V (excluding 80
V) to 176 V. If no, the mains
monitoring circuit for the power
module is faulty. Replace the
faulty module.
1. Check the bypass input voltage
or cable connections with a
multimeter.
2. Check the voltage system and
bypass voltage thresholds
configured on the LCD.
1. Check the bypass input voltage
or cable connections with a
multimeter.
2. Check the bypass input
frequency. Check the rated
frequency and frequency range
configured on the LCD.
Check whether the cable phase
sequence is correct using a
multimeter. If no multimeter is
available, exchange the positions
of any two cables.
1. Secure or connect the neutral
wire to the cabinet if it is loose
or disconnected.
2. Check that the neutral wire to
the power distribution system
is normal.
1. Check whether battery
polarities are correctly
installed by using a
multimeter. If no, correct the
installation.
2. Check whether the battery
258