UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Alarm ID
Alarm Name
(Alarm
ID-Cause
ID)
0088-1
Rack address
conflict
0089-1
Rack output
overload
0090-1
Dry contact board
fault
0090-2
0356
Battery Mode
0359
No power supplied
0332
Output disabled
0337
PDC bypass input
breaker open
0338
PDC output breaker
open
PDC Maint. breaker
0341
closed
0342
Mains input breaker
open
Issue 11 (2019-12-20)
Severity
Cause
Critical
The configured rack
address conflicts
with another one.
Minor
The load is
excessive.
The rack
capacity setting
is not
appropriate.
Critical
I2C communication
with the dry contact
board MUE05A
fails.
I2C communication
with the dry contact
board MUE06A
fails.
Minor
The UPS is working
in battery mode.
Warning
No power is
supplied.
Minor
The output is
disabled.
Critical
The bypass input
circuit breaker on
the PDC is OFF.
Critical
The output circuit
breaker on the PDC
is OFF.
The maintenance
Minor
circuit breaker on
the PDC is ON.
Critical
The mains input
circuit breaker is
OFF.
Copyright © Huawei Technologies Co., Ltd.
B Alarm List
Solution
Check the rack address setting.
Check the load and remove
some loads or expand the UPS
power capacity if the UPS is
overloaded.
Check that the configured rack
capacity meets requirements.
Replace the dry contact board
MUE05A.
Replace the dry contact board
MUE06A.
The running status is displayed.
See details about how to handle
other alarms.
The running status is displayed.
See details about how to handle
other alarms.
The running status is displayed.
See details about how to handle
other alarms.
The running status is displayed.
No further measures are required.
1. Check that all UPS output
circuit breakers are ON.
2. On the LCD, check that PDC
output breaker open alarm
has disappeared. If the alarm
persists, tap the Clear Fault
button to clear the alarm.
The running status is displayed.
No further measures are required.
The running status is displayed.
No further measures are required.
264