50 kva power modules
Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Table 3-4 Power cable terminal requirements for the UPS5000-E-200K-FM
Port
Description
Mains input
Bypass input
Battery input
Output
PE
Table 3-5
Table 3-5 Power cable terminal requirements for the 300 kVA cabinet
Port
Description
Mains input
Bypass input
Battery input
Output
PE
Table 3-6 Recommended upstream input and downstream output circuit breakers
Model
UPS5000-E-200K-
SM/FM
Issue 11 (2019-12-20)
Connection
Method
Crimped OT
terminals
Crimped OT
terminals
Crimped OT
terminals
Crimped OT
terminals
Crimped OT
terminals
lists the requirements for power cable terminals of the UPS5000-E-300K-SM/SMT.
Recommended
Connection
Method
Crimped OT
terminals
Crimped OT
terminals
Crimped OT
terminals
Crimped OT
terminals
Crimped OT
terminals
UPS
Capacity
50 kVA
Copyright © Huawei Technologies Co., Ltd.
Bolt
Bolt Hole
Specifications
Diameter
M10
10.5 mm
M10
10.5 mm
M12
13.5 mm
M10
10.5 mm
M10
10.5 mm
Bolt
Bolt Hole
Specifications
Diameter
M12
13.5 mm
M12
13.5 mm
M12
13.5 mm
M12
13.5 mm
M12
13.5 mm
Component
Mains input circuit breaker
Bypass input circuit breaker
3 Installation
Bolt
Torque
Length
40 mm
26 N· m
40 mm
26 N· m
60 mm
46 N· m
40 mm
26 N· m
30 mm
26 N· m
Bolt
Torque
Length
45 mm
46 N· m
45 mm
46 N· m
45 mm
46 N· m
45 mm
46 N· m
30 mm
46 N· m
Specifications
a
160 A/3P
100 A/3P
55