Huawei UPS5000-E Series User Manual page 166

50 kva power modules
Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Input Settings
Figure 4-23 Input settings
Item
D.G. mode
D.G. power
limiting (kVA)
D.G. charger
power ratio (%)
Input cur.
limiting
Input cur.
limiting ratio
(%)
Issue 11 (2019-12-20)
Description
Set this parameter to Enable
when a D.G. connects to the
input PDC. The UPS enters the
D.G. mode when a D.G. is
detected over dry contacts.
Set these two parameters to
control the valid input current
and limiting input current, which
prevents load impact and
facilitates better cooperation
between the UPS and the D.G.
Specifies whether to enable or
disable input current limiting to
protect generators.
Limits the input current to protect
the D.G.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Disable
Disable, Enable
Depends on the
0 kVA to 5000
actual model.
kVA
0
0%–100%
Disable
Disable, Enable
200%
50%–200%
156