UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Figure 4-61 RCCMD function enabled
SSL Encrypted Transmission
The SSL encrypted transmission set on the page of the UPS5000 monitor display module
(MDU) must be the same as the setting on the RCCMD client.
SSL Encrypted Transmission is set to Enable by default, as shown in
to Disable, the RCCMD certificate controls will not be displayed on the page, as shown in
Figure
a risk will be displayed.
Issue 11 (2019-12-20)
4-63. If SSL Encrypted Transmission is set to Disable, a message indicating there is
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Figure
4-62. If it is set
204