Communications Menu Item Descriptions - Siemens MJ-4 Series Installation Manual

Communications module, fiber optic and rs-232/485, for mj-4a, mj-xl and mj-x control panels
Table of Contents

Advertisement

Protocol
Comm Baud
Comm Parity
Comm Addr
Resync Time
Tx En Delay
DNP dl Confirm
CM SW Repeat
En
Host Addr
CM Unsolicited
AutoInhEnRemRL
DNPset
CM Vers

7.5.1 Communications Menu Item Descriptions

Data Stat, DatPortBaud, Data Parity, and DataPortAddr
These menu items apply only to the Data Port located on the front of the MJ-4 Control Panel, and do not require
modification.
Reg Id (Regulator Identification)
This item allows you to uniquely identify each regulator in the system. The Regulator Id is accessible as a data item
via the communications module for most of the protocol selections.
Protocol
This item defines the protocol selection for the MJ-4 Communications Module. The selections are listed in Table
7-4.
2200NOA is a variation of the 2200 protocol with the address field suppressed. It is provided for testing the MJ-4
Communications Module with the MJXplorer™ software. The SPECIAL item allows a new protocol handler to be
included in the Communications Module code without forcing a modification to the Main Processor code (for the
protocol selection front panel screen).
Comm Baud
This menu item defines the data rate for the MJ-4 Communications Module. The standard asynchronous
communications data rates are available for selection. For proper communications, the Comm Baud setting must
match the baud setting of the other communicating device(s) in the network.
Comm Parity
This configuration item defines the parity selection for the communications module. For proper communications,
the Comm Parity setting must match the parity setting of the other communicating device(s) in the system.
18
Communications Module protocol
Communications Module baud
(transmission rate)
Communications Module parity
Communications Module address
Communications Module resync time
(in characters)
Communications Module Transmit
Enable Delay (in milliseconds)
Confirm DNP Data Link
Enable software auto-repeat in Comm
Module
Host Address of RTU for unsolicited
responses
Comm Module can send unsolicited
response
Require Auto Inhibit to be active
before a remote raise or lower request
is acknowledged
Choose to set up your own DNP points
or use a preconfigured set
Communications Module software
version
DNP3.0, 2200, 2200NOA, MJ3A A,
MJ3A B1, MJ3A B2, 2179, 2179 MJ-
X, 2179 5A, SPECIAL
300, 1200, 2400, 4800, 9600, 19200
None, Odd, Even
0 – 65,535
0-250
0-250
No, Yes
No, Yes
0 – 65,535
No, Yes
No, Yes
DNPcfg, 2.x4, 2.x3, small2.x3, Simple,
Metering, Active, set7, set8, set9,
set10, set11, set12, set13, set14, set15
X.XX