Connecting The Protective Equipotential Bonding Conductor - MBO RW500 Operating Manual

Rewinder
Table of Contents

Advertisement

7.3.5

Connecting the protective equipotential bonding conductor

2
1
1 Cable grommet
Illustration 46: Connection of protective equipotential bonding conductor
Rewinder RW500
CAUTION
Discharge currents greater than 10 mA.
Non-observance could result in property damage.
Connect the protective equipotential bonding conductor to the PE
terminals.
Cross-section 10 mm
The RFI filters of the frequency converters used generate a system-condi-
tioned grounding leakage current.
Since this can be greater than 10 mA, according to EN 60204-1 Clause
8.2.8 a protective equipotential bonding conductor is necessary.
This should have a cross-section of 10 mm
Procedure:
1)
Insert the protective equipotential bonding conductor into the main
control cabinet through the cable grommet (1).
2)
Connect the protective equipotential bonding conductor to the PE con-
nection terminal strip (2).
The protective equipotential bonding conductor is connected.
Installation, commissioning
Making the stationary mains connection
2
(Cu).
2 PE connection terminal strip
2
.
93