7.3.3

Observe the design of the stationary mains connection

Electrical supply
Nominal voltage
3 x 400 V + N + PE
Design according to
DIN EN 60204-1,
Clause 4.3.1
Table 25: Design of the stationary mains connection
1) Prerequisite, see chapter "7.3.5 Connecting the protective equipotential bonding conductor".
Rewinder RW500
• The customer's grounding system should have as small a grounding re-
sistance as possible (optimal would be a value < 2 Ohm), since with rel-
atively high grounding resistance levels (> 50 Ohm) the EMC filters
hardly have any more filter effect.
• The N conductor is loaded (for 400 VAC power supply).
• A right rotating field is absolutely necessary.
• The machine sockets of the MBO machines may be used exclusively for
the connection of MBO folding units, units, or deliveries.
The 230 VAC sockets of the MBO machines may be used exclusively
for connecting auxiliary devices intended for this purpose, such as glu-
ing devices.
• All sockets (400 VAC and 230 VAC sockets) of the MBO machines
must be monitored at all times according to the corresponding federal
and local codes, guidelines and other regulations.
Connecting line
Cable
Five-pin copper cable (L1,
L2, L3, N, PE):
Single-conductor or multi-
conductor with connector
sleeves, make connection
touch-proof, clockwise
rotating field.
Protective equipotential bonding
(Second, additional PE conductor)
Installation, commissioning
Making the stationary mains connection
Cross-section
PE conductor
Design according to
Design according to
VDE 0100 Part 430
VDE 0100 Part 540
(IEC 60364-4-47)
(IEC 60364-5-54)
1)
Cross-section
Design according to VDE 0100 Part 540
(IEC 60364-5-54) and EN 60204-1, Clause
8.2.8
2
Cross-section = 10 mm
(Cu).