Ground AC Load Center More Than 50 ft. (15.2 m)
from Media Gateway
1
Mount the single-point ground block to any surface between the media gateways and the
AC load center single-point ground. The single-point ground block must be mounted to a
non-metallic surface.
At the bottom rear of the first media gateway, connect a 6 AWG (#40) (16 mm
2
gateway GROUND wire to the media gateway ground block. See
Gateway Grounding Wiring Diagram'' on page
3
Route the opposite end of the wire to the single-point ground block and connect.
4
At the next (if provided) DC Power media gateway, connect a 6 AWG (#40) (16 4 mm
media gateway GROUND wire to the media gateway ground terminal block GROUND
DISCHARGE bar.
Route the media gateway GROUND wire to first media gateway and connect to the
5
single-point ground block and connect block.
NOTE:
If a media gateway is located remotely (in a separate room or building), route the media
gateway media gateway GROUND wire to an approved protective ground.
6
Repeat connecting each media gateway to the single-point ground block.
Connect a 6 AWG (#40) (16 mm
7
ground block.
Route the ground wire to the AC load center ground and connect.
8
Installing an Avaya MCC1 Media Gateway
76.
2
) ground wire to an unused terminal on the single-point
October 2002
2
) media
''Typical Media