Typical Media Gateway Ground Location
1
Figure notes
First Media Gateway
1
Additional Media Gateways (if
2
installed)
3
6 AWG (#40) (16 mm
Gateway GROUND Wire
Media Gateway Ground Terminal
4
Block
Ground AC Load Center More Than 50 ft. (15.2 m)
from Media Gateway
Mount the single-point ground block to any surface between the media gateways and the
1
AC load center single-point ground. The single-point ground block must be mounted to a
non-metallic surface.
2
At the bottom rear of the first media gateway, connect a 6 AWG (#40) (16 mm
gateway GROUND wire to the media gateway ground block. See
Gateway Grounding Wiring Diagram'' on page
Route the opposite end of the wire to the single-point ground block and connect.
3
4
At the next (if provided) DC Power media gateway, connect a 6 AWG (#40) (16 4 mm
media gateway GROUND wire to the media gateway ground terminal block GROUND
DISCHARGE bar.
3
2
4
4
2
) Media
May 2002
Installing the S8700 Multi-Connect
Installing an Avaya MCC1 Media Gateway
3
5
6
2
4
widmgrnd LJK 092697
AC Load Center Single-Point Ground
5
Less than 50 Wire feet (15.2 m)
6
7
10 AWG (#25) (6 mm
to CBC
54.
7
3
2
) Ground Wire
2
) media