Duplex Reliability Configurations; High/Critical Reliability Configurations - Avaya S8700 Installing Manual

With media gateways
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

NOTE:
The Host Table should be empty. If not, in the following commands use a host table entry
that is currently unassigned.
11
Type HI1 198.152.254.201 and press
Type TL1 3 and press
12
13
Type TT1 1 and press
Type HS and press
14
Type CF and press
15
16
Type SA and press
When completed, disconnect the services laptop computer from the UPS.
17
Connect one end of a CAT5 cable to the RJ45 connector on the UPS 1 SNMP module
18
and the other end to the next available port on an Ethernet switch for Control Network A
(CNA).
Repeat steps 5 thru 18 for the UPS 2 SNMP module. Depending on the reliability
19
configuration to be installed use the following address, mask, and gateway information:

Duplex Reliability Configurations

For duplex reliability configurations use the following address and cable connection
information:
NOTE:
For duplex reliability configurations there are two servers and two UPS units. However,
there is only one control network. The following entries provide addresses on CNA for
UPS 2.
UPS IPaddress / Subnet mask = 198.152.255.238 / 255.255.255.0
Default Gateway IP address = 198.152.254.202
Host Table trap receiver IP address = 198.152.254.202
Local network administrator supplied information as required for Get and Set
community name strings.
Cable the RJ45 connector on the UPS 2 SNMP module to the next available port on the
Ethernet switch for Control Network A (CNA).

High/critical reliability configurations

For high and critical configurations use the following addresses and cable connection
information:
UPS IPaddress / Subnet mask = 198.152.255.239 / 255.255.255.0
Enter.
(Sets the trap level for the host, All traps)
Enter.
(Sets the trap type, Standard UPS MIB-defined)
Enter.
Verify the table entries. (Re-displays the host table)
Enter.
(Re-displays the basic administration screen)
Enter.
(Saves configuration and restarts module)
Enter.
October 2002
(Sets the trap destination for this UPS 1)
53
Configure the UPSs