Connect Dc Power Distribution Unit Ground - Avaya S8700 Installing Manual

With media gateways
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

108
Installing an Avaya SCC1 Media Gateway Stack
Frame Ground Wiring Between cabinet and Battery Cabinet
Figure notes
1
2
3
4

Connect DC Power Distribution Unit Ground

1
Measure and cut a length of 6 AWG (#40) (4 mm
the GROUND DISCHARGE bar in the DC power cabinet and the GRD connector on the
DC-powered Distribution Unit. See
page
At the cabinet, connect a the 6 AWG (#40) (16 4 mm
2
DISCHARGE bar.
Route the opposite end of the wire to the DC-powered Distribution Unit and connect the
3
wire to the GRD connector.
4
Repeat Steps 2 and 3 for each remaining DC-powered Distribution Unit.
3
2
6 AWG (#40) (4mm
) Wire
DC Battery Cabinet
DC power cabinet
Grounding Hole in Top of cabinet
109.
1
5
Terminal Lug (Part of D-18181895)
6
Pan Head Slotted Screw
Star Washer
7
8
Hex Nut
2
) wire long enough to reach between
''Ground for the DC-Powered Distribution Unit'' on
October 2002
2
dc_rect6 RBP 052996
2
) wire to the GROUND