Install Connector Cables Between Auxiliary
Cabinet and MDF
Auxiliary equipment that connects to the MDF can be mounted inside the Auxiliary cabinet.
The equipment connects to an ED-1E1443-10 (Group 1) intraconnection panel mounted in the
cabinet. This intraconnection panel consists of a 110-type 100-pair wiring block. Auxiliary
equipment is connected to the 110-type wiring block. The wiring block is pre-wired to four
25-pair female connectors mounted on the outside rear of the cabinet.
1
Install "D" rings on the wall between the cable slack manager and the
terminal/connecting blocks mounted on the MDF.
2
Install a self-sticking port label on the rear of each connector on the B25A connector
cable. See
''Self-Stick Label on 25-Pair Cable Connector'' on page
3
Labels should be positioned so they will not be obscured by the cabinet connector
retainers.
4
At the rear of the Auxiliary cabinet, connect 1 end of the connector cable to the assigned
connector.
Route the cable down the rear of the cabinet and through the cable slack manager to the
5
MDF.
At the MDF, connect the other end of the cable to the assigned terminal/connecting block
6
connector.
Store the excess cable in the cable slack manager.
7
Repeat Steps 2 through 6 until all cables are installed.
8
Self-Stick Label on 25-Pair Cable Connector
Patch Cord/Jumper Installation and Administration
May 2002
Installing the S8700 Multi-Connect
131.
157