Installing the S8700 Multi-Connect
Testing the Complete Configuration
Stratum 3 Clock LED Indicators — Continued
Card
CI
ST3
ST3
ST3
ST3
TOCA
TOCA
Verify Timing to the Media Server
1
2
3
NOTE:
Wait 1 minute for the software to reconfigure the media server synchronization.
4
If test 649 is successful, then the media server is getting correct timing from the Stratum 3
clock.

Resolve Alarms

As a last step, inspect the alarms log.
Use the media server web interface.
1
LED Label
Procedure
FAIL
Check wiring for its associated DS1 reference and replace the
circuit pack if necessary
FAIL
Replace the circuit pack
LOCK
Ignore this LED
HOLDOVER
Ignore this LED
FREE RUN
Ignore this LED
FAIL
Replace the circuit pack
PORT ALM
Replace the circuit pack if necessary
To administer the Stratum 3 clock, type change synchronization and press
Type 3 in the stratum field.
Type the port network number where the TN780 Tone-Clock circuit packs reside in the
port network field.
Verify the results of test 649. If test 649 fails with a code of 2101, then check the wiring
for EXTSYN0 and EXTSYN1. Refer to the maintenance book for your configuration
Click on View Current Alarms and see if any alarms were generated. If so, resolve any
alarms that may exist using the maintenance book for your configuration
May 2002
.
Enter
.
.