Task List: Connect Ac Power And Ground; Power Requirements; Power Supply Sources (J58890Ce-1, J58890Ce-2, And J58890Ch-1) - Avaya S8700 Installing Manual

For multi-connnect configurations
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

50
Installing the S8700 Multi-Connect
Installing an Avaya MCC1 Media Gateway
For information about connecting AC power and ground, see:

Task List: Connect AC power and ground

Perform these tasks to connect AC power and ground:
1
2
3
4
5

Power Requirements

s8700 Multi-Connect configuration Power Requirements
Maximum DEFINITY UL Rating Label Power Capacity
208
240
120
Power Supply Sources (J58890CE-1, J58890CE-2,
and J58890CH-1)
The connect AC power and ground procedures apply to the AC-powered media gateways.
Any of these power sources can supply 60 Hz power to the AC load:
''Power Requirements'' on page 50
''Power Supply Sources (J58890CE-1, J58890CE-2, and J58890CH-1)'' on page 50
''Connect Mixed AC/DC Power and Ground'' on page 67
on page 57
''Connect AC Power'' on page 59
Iac I n
Max W I n
24
3245
21
3276
40
3120
Single-phase, 4-wire, 120/240 VAC supplying 240 VAC.This source has 2 hot wires, 1
ground wire, and 1 neutral wire (J58890CE).
Single-phase, 4-wire, 120/208 VAC supplying 208 VAC. This source has 2 hot wires, 1
ground wire, and 1 neutral wire (J58890CE).
Single-phase, 3-wire, 208 or 240 VAC. This source has 2 hot wires and 1 ground wire
(J58890CH).
or
''Connect Large Battery Holdover''
BTU/Hr.
11071.26
11177.71
10645.44
May 2002
or

Advertisement

Table of Contents
loading