Earthquake Mounting — Raised Computer Floor
4 inches
(10.16 cm)
raised

Connect AC Power and Ground

!
CAUTION:
The equipment room AC power and ground wiring must be performed by a qualified
electrician. Refer to Designing the Avaya S8700 Media Gateway Multi-Connect
Configuration for site requirement information.
!
CAUTION:
The power circuit must be dedicated to the S8700 Multi-Connect configuration and must
not be shared with other equipment and must not be controlled by a wall switch. The AC
receptacle should not be located under the MDF.
!
CAUTION:
S8700 Multi-Connect configuration grounding must comply with the general rules for
grounding contained in Article 250 of the National Electrical Code (NEC), National Fire
Protection Agency (NFPA) 70, or the applicable electric code in the country containing the
equipment. For more information, refer to
variable
floor
height
concrete
subfloor
May 2002
Installing the S8700 Multi-Connect
Installing an Avaya MCC1 Media Gateway
3/8 - 16
threaded rod
3/8 - 16
Concrete floor
anchor
Approved
Grounds.
3/8 inch
flat washer
Nut welded
to frame
Leveling
foot
cab_base CJL 052096