Connect AC Power

Set the main circuit breakers on the power distribution unit OFF.
1
2
Connect media gateway AC line cords to the AC power receptacles.
NOTE:
Do not power up the S8700 Multi-Connect configuration at this time.

Connect DC Power and Ground

!
CAUTION:
Grounding of the S8700 Multi-Connect configuration shall comply with the general rules
for grounding contained in Article 250 of the National Electrical Code, NFPA 70. For
more information, refer to
The grounding methods for the DC-powered S8700 Multi-Connect configuration are more
complex than that of an AC-powered S8700 Multi-Connect configuration.
ground layout for a DC power cabinet. The size of the wire required for the -48 volt DC and -48
volt return must ensure the voltage supplied by the battery plant is maintained between -42.5
and -54.2 volts DC at all times for proper operation and to prevent hardware damage. The wire
must be sized for a maximum voltage drop of 0.5 VDC in each leg of the DC distribution.

Task List: Connect DC Power and Ground

Perform these tasks to connect DC power and ground, power distribution unit (J58890CH-1
Only):
Perform these tasks to connect DC Power and Ground (J58890CF Only):
NOTE:
These installation tasks correspond to the numbers in
''Connect Grounds for DC Battery and Power Cabinets'' on page 64
Approved
Grounds.
60:
May 2002
Installing the S8700 Multi-Connect
Installing an Avaya MCC1 Media Gateway
shows a typical power and
''Typical Power and Ground for a