Install the Stratum 3 clock

1
2
3
4
''Connect DC Power and Ground to Stratum 3 Clock Cabinet'' on page 108
5
6
7
8
9
10

Unpack and Inspect Stratum 3 Clock Cabinet

Check the status of the SHOCKWATCH and/or TILTWATCH indicators on the
1
cardboard container. If the container has been jarred or tilted beyond specifications, the
indicators are red, indicating possible damage.
Remove all packing material.
2
Remove front door and rear screw-on panels from the cabinet.
3
Inspect the cabinet for damage. Report any damage per local instructions.
4

Install and Position Stratum 3 Clock Cabinet

Check the location of the AC power receptacle. The receptacle must be on a separately fused
circuit that is not controlled by a wall switch. It must be located within 10 ft. (3 m) of the
cabinet and should be located outside the MDF area.
1
Position the clock cabinet in the designated location.
2
If earthquake protection is required, skip
SCC1 Media Gateway'' on page 80
Gateway'' on page 46
3
If earthquake protection is not required, level the cabinets and adjust and lock the cabinet
stabilizing bolts to keep the cabinet from moving.

Connect AC Power to Stratum 3 Clock Cabinet

The clock cabinet requires a 120 VAC, 15 amp receptacle. The green wire ground provided by
the receptacle is sufficient. The clock cabinet does not require a ground connection back to the
single-point ground.
to''Install Earthquake Protection for Avaya
or
''Install Earthquake Protection for Media
May 2002
Installing the S8700 Multi-Connect
Install the Stratum 3 clock
107