3. WP8010 INSTALLATION
Option
62:RECENT CLOSE
63:ZONE RESTORE
64:SYST.INACTIVE
1
65:TWO WAY VOICE
Send 2wv code
Voice <- -> C.S.
Ringback time
Ambient level
(Return)
Master Installer only for
Send 2wv code /
Voice <--> C.S. /
Ringback time
Send 2wv code
Voice <- -> C.S
Ringback time
Ambient level
66:24H ZONE RPRT
Applicable in UK only
1
Refers to WP8030 with voice option only
54
Configuration Instructions
False alarms may occur if users do not exit the premises within the exit delay period, resulting
in a false alarm a short time later. In such cases, inform the Monitoring Station that the alarm
occurred shortly after the system was armed (this event is known as "Recent Close"). The
report enabled option sends a "recent closing" report to the Monitoring Station if an alarm
occurs within 2 minutes from the end of the exit delay.
Options: report disabled (default) and report enabled
Notes:
1. CP-01 was tested and certified by ETL/Intertek.
2. CP-01 features not to be enabled in UL Listed product.
Some Monitoring Stations require that following an alarm event from a specific zone, the
system will also report when the alarming zone has restored to normal.
Options: report enabled (default) and report disabled
The WP8010/WP8030 can report a "System Inactive" event message (CID event 654) to the
Monitoring Station if the system is not used (i.e. armed) during a predefined time period.
Options: report disabled (default); after 7/14/30/90 days.
You can configure the two way voice channel settings of the control panel
Send 2 WV Code: Define whether the system will send two-way voice code to the Monitoring
Station (to turn the Monitoring Station from data communication to voice communication state)
by using pre-selected SIA or Contact-ID communication format only.
Voice <--> C.S.: Select the timeout for 2-way voice communication with Monitoring Stations, or
enable the Monitoring Station to ring back for 2-way voice function. This option is applicable only
after reporting an event to the Monitoring Station for listening and speaking.
Ringback Time: Define the period during which the Monitoring Station can establish 2-way
voice communication with the control panel
A. Alarm type message was received by Monitoring Station.
B. Ring Back function was selected (see "Voice <--> C.S." sub menu above).
Ambient Level: Select the ambient noise level of the installation. If it is a relatively noisy
environment, set it to High (default setting). If it is a very quiet environment, set to Low.
Note: Two-way voice not to be enabled on UL Listed product.
Options: disable (default); and enable.
Options: disable (default); timeout 10/45/60/90 s; timeout 2 m; and ringback.
Note: If "ring back" is selected, you should select "disable report" for private telephone (see
Option "01:REPORT EVENTS"), otherwise the Monitoring Station will establish communication
1
with the control panel
(after an event occurrence) in the normal manner (and not after one ring).
Options: 1 (default)/3/5/10 minute(s).
Options: low (default); and high.
Define whether 24 hour (silent and audible) zones will function as normal 24 hour zones or as
panic zones.
Options: audibl as panic; silent as panic; both as panic; and both burglary (default).
1
(after 1 ring), if:
D-306233 CUSDOC PM-10/30 V18 DSC TRIPLE EN INST
1
, as follows: