When multiple outdoor units are to be installed, if they cannot be installed against a wall or
the local outdoor temperature may be below –5° C, place an air baffle at the air intake side of
each outdoor unit.
Figure 3-11 Space requirements for installing multiple outdoor units

3.4 Layout Principles

The layout principles are as follows:
Issue 05 (2019-12-20)
Figure 3-10 Requirements for installing an outdoor unit on a wall
The bearing capacity of the support platform is more than 230 kg.
Reserve no less than 300 mm from the left or right side of the outdoor unit for maintenance
personnel to walk.
Grid structure is recommended to avoid the air exhaust and intake of the smart cooling product being
affected by an guardrail structure.
The picture is only for reference, adjust based on the actual situation if necessary.