NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)

3.2.4 Cables

Table 3-5
protective hoses.
Table 3-5 Cable specifications
Application
Scenario
Indoor unit power
cable (optional)
Outdoor unit
power cable
(optional)
Signal cable to
the indoor and
outdoor units
(optional)
Issue 05 (2019-12-20)
The height of the U-shaped pipe clamp is 5 mm less than the pipe diameter (including the thermal
insulation foam). Pipe supports are subject to engineering procurement.
It is recommended that pipe supports and pipe clamps be made of 304 stainless steel.
Install a support every 1500 mm for the straight sections of pipes, and 500 mm away from each
bending point in turning sections.
The site ground resistance must be less than 0.1 ohm.
The fireproof level of the cables must be at least VB.
The signal cables of indoor and outdoor units must be shielded cables, and the shielding
layer must be reliably grounded.
lists the cables to be connected onsite. When connecting cables, fit them with
Specifications
Electrical power cable, 600 V/1000 V,
ZA-RVV, 5 x 6 mm
46 A, outdoor cable, CE
Naked crimping terminal: OT, 6 mm
50 A, tin plating, 12-8 AWG
Electrical power cable, 600 V/1000 V,
ZA-RVV, 3 x 6 mm
wires), 46 A, outdoor cable, CE
Naked crimping terminal: OT, 6 mm
50 A, tin plating, 12-8 AWG
Electrical power cable, 300 V, SJTW, 3 x 16
AWG, black (three core wires), 10 A,
shielded outdoor cable, UL
Naked crimping terminal, single-wire cord
end terminal, 1.5 mm
Copyright © Huawei Technologies Co., Ltd.
2
, black (five core wires),
2
, M6,
2
, black (three core
2
, M6,
2
, 16 A, Red
3 Installation Guide
Remarks
Cable should not be
lighter than normal
PVC sheathed flexible
cord (IEC 60227 53).
The length is
determined by site
survey.
Delivered with the
fittings
Cable should not be
lighter than
chloroprene rubber
armored flexible cord
(IEC 60245 57). The
length is determined
by site survey.
Delivered with the
fittings
The length is
determined by site
survey.
Delivered with the
fittings
32