Huawei NetCol8000-A013 User Manual page 177

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
Menu
Setting > Admin Menu >
System Setting > Outdoor Fan
Setting > Admin Menu >
System Setting > EEV
Issue 05 (2019-12-20)
Name
Stop Delay
Min Speed
Max Speed
Min Run Pressure
Start Pressure
Max Run Pressure
Min Open
Max Open
Standby Open
Suct Super Heat Set point
Suct Super Heat Dead zone
Adjust Cycle
P-band
Intergral Time Constant
Diff Time Constant
Ultralow Press Ini Open
Low Press Ini Open
Medium Press Ini Open
High Press Ini Open
Copyright © Huawei Technologies Co., Ltd.
E Controller Menu
Default
Settings Range
Value
30s
0 to 99s
27.5%
20% to 40%
100%
40% to 100%
2.10 MPa
1.0 MPa to 3.5 MPa
2.26 MPa
1.0 MPa to 3.5 MPa
2.80 MPa
2.5 MPa to 4.0 MPa
52step
0 to 480 step
480step
0 to 480 step
300step
Min Open to Max Open
6.0° C
2.0° C to 20.0° C
2.0° C
0 to 5.0° C
10s
5s to 300s
2.0
0.1 to 10.0
60s
1s to 999s
0
0 to 999s
180step
Min Open to Max Open
150step
Min Open to Max Open
120step
Min Open to Max Open
120step
Min Open to Max Open
170