Pipes - Huawei NetCol8000-A013 User Manual

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
Temperature
(° C)
13
14
15
16
17
18

3.2.2 Pipes

Oil Trap
Figure 3-2
Figure 3-2 Oil trap (unit: mm)
Gas Pipe, Liquid Pipe, and Thermal Insulation Foam (Optional)
Table 3-4
Table 3-4 Specifications
Item
Liquid pipe
Issue 05 (2019-12-20)
Saturation
Pressure-S
urface
Pressure
(MPa)
1.09
1.12
1.16
1.19
1.23
1.27
shows the oil trap specifications.
lists the specifications for pipes and thermal insulation foam.
Copyright © Huawei Technologies Co., Ltd.
Temperature
Saturation
(° C)
Pressure-S
urface
Pressure
(MPa)
32
1.89
33
1.94
34
1.99
35
2.04
36
2.1
37
2.15
Specifications
3/8 inch (9.52 mm), wall thickness: 0.75 mm;
pressure withstanding capacity ≥ 4.5 MPa
3 Installation Guide
Temperatur
Saturati
e (° C)
on
Pressure
-Surface
Pressure
(MPa)
51
3.04
52
3.11
53
3.19
54
3.26
55
3.34
N/A
N/A
29

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol500-a022

Table of Contents