Huawei NetCol8000-A013 User Manual page 79

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
Setting
Item
Enable
Teamwork
Resistor
Units in
Group
Active
Units in
Group
Rotation
Function
Rotation
Type
Rotation
Cycle
Rotation
Time
High Temp
Issue 05 (2019-12-20)
Description
Indicates the build-out
resistor status of each
smart cooling product
in a teamwork group.
Indicates the number of
smart cooling products
in a group. The value is
an integer ranging from
1 to 32.
Indicates the number of
running units in a
group. The value is an
integer ranging from 1
to the number of units
in a group.
Indicates whether to
disable or enable the
active and standby
smart cooling products
to work alternatively to
maximize their service
life.
Can be set to Address
or hour
Indicates the interval
between rotations. The
value ranges from 1 to
30.
Indicates the time when
rotation takes place.
The value can be any
hour in a day (0–23).
When it is enabled, if
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Setting Principle
Set this parameter
to No for
non-teamwork
scenarios.
For teamwork
scenarios, set this
parameter to Yes
for the first and last
smart cooling
products in a
teamwork group,
and set it to No for
other smart cooling
products.
Set this parameter to
the number of smart
cooling products in a
group.
Assign the address 1 to
the master unit, and
assign addresses
starting from 2
consecutively to all
running units in a
group. Remaining units
will be regarded as
standby units.
It is recommended that
the function be enabled
when the load power is
even.
You are advised not to
change the value.
N/A
N/A
You are advised not to
Default Value
--
3
2
Disable
Address
1D
00:00
Disable
72