Huawei NetCol8000-A013 User Manual page 175

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
Menu
Setting > Admin Menu > Alarm
Setting > Electric Heater
Setting > Admin Menu > Alarm
Setting > Wet Film Humidifier
Setting > Admin Menu > Alarm
Setting > Delete All Historical
Alarms
Setting > Admin Menu >
System Setting > System
Control
Setting > Admin Menu >
System Setting > Temp&Humid
Sensor
Issue 05 (2019-12-20)
Name
Air Filter RT out Alarm
Smoke Sensor Alarm
Floor Water Alarm
Fire Alarm
Run Time out Alarm
Run Time out Thres
Humid RT out Alarm
Humid RT out Thres
Pump RT out Alarm
Pump RT out Thres
Delete All Historical Alarms
Forced Cooling
Dehumidifying
Humidifying
Heating
Freq Rise Temp Demand
Freq Drop Temp Demand
Heating Temp Demand
Dehumtemp Comp
Dehum Comp On Demand
Dehum Comp Off Demand
Max Temp Set
Min Temp Set
Max Humid Set
Min Humid Set
Temp P-band
Temp Deadzone
Dehum P-band
Dehum Dead zone
Copyright © Huawei Technologies Co., Ltd.
E Controller Menu
Default
Settings Range
Value
4320h
2160h to 6480h
Enable
Enable/Disable
Enable
Enable/Disable
Enable
Enable/Disable
Enable
Enable/Disable
30000
20000h to 40000h
Enable
Enable/Disable
8760h
4380h to 17520h
Enable
Enable/Disable
40000h
10000h to 50000h
No
Yes/No
Enable
Enable/Disable
Enable
Enable/Disable
Enable
Enable/Disable
Enable
Enable/Disable
50%
0% to 100%
–50%
–100% to 0%
–100%
–100% to 0%
Enable
Enable/Disable
–50 to +50%
0%
50%
0 to 100%
32.0
18° C to 35° C
18.0
18° C to 35° C
90.0%RH
20.0%RH to 100.0%RH
30.0%RH
20.0%RH to 70.0%RH
3.0° C
0.5° C to 20.0° C
1.0° C
0.1° C to 20.0° C
5.0%
1.0% to 90.0%
1.0%
0.5% to 90.0%
168