Cate
Symptom Possible Cause
gory
The
The refrigerant is insufficient.
compresso
The outdoor fan speed
r discharge
controller fails.
pressure is
too low.
Refrigerant leaks.
The outdoor temperature is too
low.
The
Refrigerant is insufficient.
compresso
Refrigerant leaks.
r suction
pressure is
too low.
The condensing pressure is too
low.
Liquid is
The indoor temperature is too
low.
returning
to the
The air filter is dirty or
compresso
blocked.
r.
The electronic expansion valve
coil is faulty.
Refrigerant has been charged
too much
The
Liquid is returning to the
compresso
compressor.
r generates
too much
Refrigerant oil is insufficient.
operating
noise. (It
is common
that the
compresso
r generates
much
noise
when it
shuts
down.)
Issue 05 (2019-12-20)
Measure
Fill more refrigerant.
Replace the fan speed controller.
Apply soapy water or use a halogen leak detector to
check for any leakage. If leaking points are found,
retrieve the refrigerant and weld the leaking points
again. Contact Huawei technical support.
No action is required.
Fill more refrigerant.
Apply soapy water or use a halogen leak detector to
check for any leakage. If leaking points are found,
retrieve the refrigerant and weld the leaking points
again. Contact Huawei technical support.
Check whether the outdoor temperature is too low and
whether the outdoor fan is under control.
Increase the temperature setting.
Replace the air filter.
Replace the electronic expansion valve coil.
Reclaim part of refrigerant.
Check whether the suction superheat degree of the EEV
is within the normal ranges (normal range of the
suction superheat degree: 4–10° C).
Add refrigerant oil.
Copyright © Huawei Technologies Co., Ltd.