Step 5 Unscrew the inductor box using a Phillips screwdriver and remove the inductor.
Figure 5-16 Remove the inductor
Step 6 Install a new inductor and secure the inductor box.
Step 7 Bind cable ties and install inductor terminals according to the photo you have taken.
Step 8 Use a Phillips screwdriver to reinstall the left front panel and top cover.
Step 9 Power on the smart cooling product and ensure that it starts properly. Observe it for 30
minutes and ensure that no alarm is generated.