Huawei NetCol8000-A013 User Manual page 78

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
Figure 4-9 Teamwork setting
If the teamwork function is enabled and the unit address is set to 1 (master unit), the menus on the last
two screens are viewable and configurable. Otherwise, the last two screens are not displayed.
Step 3 Set Teamwork Function to Enable.
Step 4 Set the Unit Address of the master unit to 1 and the Unit Address of the slave unit to an
integer other than 1.
Step 5 Set other parameters based on the following table.
Table 4-4 Teamwork setting
Setting
Item
Teamwork
Function
Unit
Address
Issue 05 (2019-12-20)
Description
Indicates whether to
disable or enable the
teamwork function. If
the function is disabled,
a unit operates
independently. If the
function is enabled, a
unit operates in a team
with other units.
Indicates a smart
cooling product address
in a teamwork control
group. The address can
be set to 1 for only one
unit in each group, and
must be unique for all
other units in the
group.
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Setting Principle
Set this parameter
based on onsite heat
load distribution.
Set the planned unit
address.
Default Value
Disable
--
71