If the outdoor unit does not take the electricity from indoor unit, turn off the circuit breaker
for the outdoor unit.
Step 2 Remove the top cover and left front panel using a Phillips screwdriver.
Step 3 Use a Phillips screwdriver to remove the two screws that secure the rotate panel of the electric
control box, and rotate the rotate panel.
Figure 5-13 Opening the rotate panel
Step 4 Use diagonal pliers to cut off the cable ties that secure the module board cables, and remove
the cable terminals from the module board.
Take a photo before performing this step so that you know how to bind the cable ties and install the
cable terminals later.
Step 5 Use a Phillips screwdriver to remove the four bolts that secure the module board, and remove
the module board.