Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
Menu
Setting > User Menu > Comm
Setting
Setting > User Menu >
Password Setting
Setting > Admin Menu > Alarm
Setting > Temp&Humid Sensor
Setting > Admin Menu > Alarm
Setting > Compressor
Setting > Admin Menu > Alarm
Setting > Indoor Fan
Setting > Admin Menu > Alarm
Setting > Outdoor Fan
Setting > Admin Menu > Alarm
Setting > Main board
Issue 05 (2019-12-20)
Name
Return Air Humid Set
Baud Rate
Comm Address
Enable Monitoring Resistor
/
Return Air HT Alarm
Return Air HT Thres
Return Air LT Alarm
Return Air LT Thres
High Humid Alarm
High Humid Thres
Low Humid Alarm
Low Humid Thres
Temp&Humid Alarm Delay
Run Time out Alarm
Run Time out Thres
Start Low Press Mask Time
Run Time out Alarm
Run Time out Thres
Fan1 Run time out Alarm
Fan1 Run time out Thres
Fan2 Run time out Alarm
Fan2 Run time out Thres
Undervolt Thres
Overvolt Thres
Over Freq Thres
Under Freq Thres
Air Filter RT out Alarm
Copyright © Huawei Technologies Co., Ltd.
E Controller Menu
Default
Settings Range
Value
temperature setting
50.0
The minimum humidity
setting to the maximum
humidity setting
9600
9600/19200
Setting
1 to 255
No
Yes/No
000001
Six-digit number
Enable
Enable/Disable
32.0° C
25° C to 40.0° C
Enable
Enable/Disable
12.0° C
5° C to 24.0° C
Enable
Enable/Disable
85.0%RH
65.0%RH to 95.0%RH
Enable
Enable/Disable
10.0%RH
5.0%RH to 35.0%RH
60s
5s to 999s
Enable
Enable/Disable
30000h
20000h to 40000h
360s
0 to 600s
Enable
Enable/Disable
50000h
30000h to 80000h
Enable
Enable/Disable
40000h
30000h to 80000h
Enable
Enable/Disable
40000h
30000h to 80000h
85%
83% to 100% (220V)
110%
100% to 112% (240V)
63Hz
61Hz to 63Hz
47Hz
47Hz to 49Hz
Enable
Enable/Disable
167