Replacing An Inductor - Huawei NetCol8000-A013 User Manual

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
Procedure
Step 1 Turn off the indoor unit circuit breaker and circuit breaker in the power distribution cabinet.
If the outdoor unit does not take the electricity from indoor unit, turn off the circuit breaker
for the outdoor unit.
Step 2 Reclaim all the refrigerant from the system using a refrigerant retrieval device to ensure that
there is no pressure inside the system.
Step 3 Remove the top cover, the front panel, and the left front panel.
Step 4 Cut off the cable ties for the dryer using diagonal pliers, weld from the welding point using a
welding tool, and remove the dryer.
To avoid burning the internal components, other pipes, thermal insulation foam, power cables,
and labels, take protective measures, such as spreading wet cloth, around the welding
position.
Step 5 Weld the new dryer to the pipe. Secure the new dryer using cable ties.
Step 6 Perform a leakage test with nitrogen again. After checking that the smart cooling product does
not leak, vacuumize the smart cooling product and charge refrigerant.
Step 7 Reinstall the front panel, left front panel, and top cover.
Step 8 After power-on again, tap
compressor rotational speed to 3000 rpm.
Step 9 Choose Run > Device Run State, and read the suction pressure, discharge pressure, and EEV
suction superheat degree. Check that the values are within the normal ranges and that there
are no device abnormality alarms.
Step 10 Tap
to 0 rpm.
Step 11 Exit the diagnostic mode.
----End

5.4.2.6 Replacing an Inductor

Prerequisites
Issue 05 (2019-12-20)
> Maintain > Diagnostic Mode > Enter and set the compressor rotational speed
An inductor needs to be replaced.
A spare inductor of the same model is available and functional.
Copyright © Huawei Technologies Co., Ltd.
5 System Operation and Maintenance
> Maintain > Diagnostic Mode > Enter and set the
115

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol500-a022

Table of Contents