NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
Alarm
Alarm Name
ID
213
Comp Start
Fail Alarm
214
Comp Drive
DC Overvolt
Alarm
215
Comp Drive
DC Undervolt
Alarm
216
Comp Drive
Overheat
Alarm
217
Comp Drive
Alarm
Issue 05 (2019-12-20)
System
Possible Causes
Action
module of the compressor
drive board is faulty.
The
The difference between the
compressor
compressor control output
shuts down.
rotational speed and the actual
compressor rotational speed is
greater than the control
threshold.
The
The input voltage of the
compressor
compressor drive board is
shuts down.
higher than the preset threshold.
The
The input voltage of the
compressor
compressor drive board is lower
shuts down.
than the preset threshold.
The
Protection against overheating
compressor
of the compressor drive board is
shuts down.
triggered.
The
The compressor drive board of
compressor
the outdoor unit is faulty.
shuts down.
Copyright © Huawei Technologies Co., Ltd.
5 System Operation and Maintenance
Solution
1. Check the compressor
status.
2. Refill refrigerant.
3. Replace the compressor
drive board or compressor.
1. Check whether the input
power is within the normal
range.
2. Use an oscilloscope to check
whether the waveform of the
power grid is within the
normal range.
3. Replace the compressor
drive board if it is faulty.
1. Check whether the input
power is within the normal
range.
2. Use an oscilloscope to check
whether the waveform of the
power grid is within the
normal range.
3. Replace the compressor
drive board if it is faulty.
1. Check whether the fan speed
of the outdoor unit is
normal.
2. Check whether refrigerant in
the system is insufficient,
which causes the outdoor
unit fan to operate at a low
speed.
3. Check the installation
environment of the outdoor
unit to see whether the heat
dissipation of the outdoor
unit is poor and whether the
outdoor unit is blocked.
4. Check whether the fins of
the outdoor unit are
polluted, which causes the
air intake volume of the
outdoor unit to be small.
1. Check the compressor
status.
2. Check the connection status
of the compressor and the
88