NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
Appearance Introduction
Figure 2-5 Appearance introduction
(1) Air exhaust vent
(4) Hole
Cooling Components
The indoor unit mainly consists of the direct current (DC) fan, evaporator, electronic
expansion valve (EEV), electric heater (optional), wet film humidifier (optional), and stop
valve.
Issue 05 (2019-12-20)
DC fan
The DC axial fan is used, which supports stepless speed adjustment.
Evaporator
The evaporator adopts the inner-threaded copper pipe and blue hydrophilic aluminum
foil to prevent water blowing due to condensate water accumulation and improve heat
exchange performance. The evaporator uses the I-type design, reducing the air resistance
and improving the sensible heat ratio.
EEV
The throttling device is a name-brand EEV. The system controls the EEV to quickly and
accurately adjust the refrigerant volume based on the temperature and humidity
requirements. In this way, system stability and reliability can be ensured, and balanced
temperature and humidity can be achieved in the equipment room.
Electric heater
Copyright © Huawei Technologies Co., Ltd.
(2) LCD
(5) Key hole