Optional) Setting Monitor Parameters - Huawei NetCol8000-A013 User Manual

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
Setting
Item
Start All
Temp for
HT Start
All
Low Temp
Start All
Temp for
LT Start All
Step 6 After the setting is complete, tap
----End

4.5 (Optional) Setting Monitor Parameters

Procedure
Step 1 Choose Comm Setting from the user menu, and tap
setting screen.
Figure 4-10 Communication setting
Issue 05 (2019-12-20)
Description
the return air
temperature is higher
than Temp for HT
Start All, all the smart
cooling products in a
group will start cooling
simultaneously.
N/A
When it is enabled, if
the return air
temperature is higher
than Low Temp Start
All, all the smart
cooling products in a
group will start heating
simultaneously.
N/A
Copyright © Huawei Technologies Co., Ltd.
Setting Principle
change the value.
You are advised not to
change the value.
You are advised not to
change the value.
You are advised not to
change the value.
to return to the user menu.
to access the communication
4 Power-On Commissioning
Default Value
31° C
Disable
13° C
73

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol500-a022

Table of Contents