Operating Hours Counter - ABB CL Series Applications Manual

Logic relays
Hide thumbs Also See for CL Series:
Table of Contents

Advertisement

1SVC 440 795 M0100

Operating hours counter

I2-------ÄO1
O1uI8----RO1
h------TT1
T1-------ÄQ3
O4
S
000000
O:
The logic relay provides 4 independent operating hours
counters. These operating hours counters enables you to
record the operating hours of systems, machines and
machine parts. An adjustable setpoint can be selected within
the value range. In this way, maintenance times can be
logged and reported. The counter states are retained even
when the device is switched off. As long as the count coil of
the operating hours counter is active, the logic relay counts
the hours in one second cycles.
You integrate an operating hours counter into your circuit in
the form of a contact and coil.
Contact
Coil
O1
O4
to
ÄO1
RO1
Parameter display and parameter set for the operating hours
+
counter function block:
O4
Operating hours counter number 04
+
+
appears in the parameter display
-
appears in the parameter display
S
Setpoint in hours
O:
Actual value of the operating hours counter [h]
In the parameter display of an operating hours counter you
change the setpoint in hours and the enable of the
parameter display.
Operating hours counter
ÄO4
to
Count coil of the operating hours
counter
RO4
to
reset coil of the operating hours
counter
143