Self-Latching - ABB CL Series Applications Manual

Logic relays
Hide thumbs Also See for CL Series:
Table of Contents

Advertisement

1SVC 440 795 M0100
I1uI2----ÄQ1
Q1k
S1 n/o contact at I1
S2 n/c contact at I2
Table 21: Two-way circuit (XOR)
I1
I2
Q1
0
0
0
0
1
1
1
0
1
1
1
0

Self-latching

A combination of a series and parallel connection is used to
wire a latching circuit.
Latching is established by contact Q1 which is connected in
parallel to I1. If I1 is actuated and reopened, the current
flows via contact Q1 until I2 is actuated.
Table 22: Self-latching
I1
I2
Contact Q1
0
0
0
0
1
0
1
0
0
1
1
0
0
0
1
0
1
1
1
0
1
1
1
1
Latching circuits are used to switch machines on and off. The
machine is switched on at the input terminals via n/o contact
S1 and is switched off via n/c contact S2.
S2 breaks the connection to the control voltage in order to
switch off the machine. This ensures that the machine can be
switched off, even in the event of a wire break. I2 is always
closed when not actuated.
Basic circuits
Coil Q1
0
0
0
1
0
1
0
1