ABB CL Series Applications Manual page 155

Logic relays
Hide thumbs Also See for CL Series:
Table of Contents

Advertisement

Wiring with the logic relay
152
h
You can only use analog values as setpoints if the value of
the analog input is stable. Fluctuating analog values
reduce the reproducibility of the time value.
The following conversion rules apply if you are using variable
values such as an analog input:
s time base
Equation: Time setpoint = ( Valuex10) in [ms]
Value, e.g. Analog
input
0
100
300
500
1023
M:S time base
Rule:
Time setpoint = Value divided by 60,
integer result = Number of minutes, remainder is the number
of seconds
Value, e.g. Analog
input
0
100
300
500
1023
1SVC 440 795 M0100
Time setpoint in [s]
00.00
01.00
03.00
05.00
10.23
Time setpoint in
[M:S]
00:00
01:40
05:00
08:20
17:03