Function Of The Analog Value Comparator Function Relay - ABB CL Series Applications Manual

Logic relays
Hide thumbs Also See for CL Series:
Table of Contents

Advertisement

1SVC 440 795 M0100
i
A1 LT
I1
I7
F1
+0
I2
0100
F2
+0
OS
+0
HY
0025
A1-------ÄQ1
Function of the analog value comparator function
relay
h
The GT, GE, LT, and LE comparison functions only differ in
the fact that GE and LE also switch when the value is equal
to the setpoint. To ensure that all analog value
comparators of AC010 devices are compatible with the
logic relays, the CL-LSR/CL-LST and the CL-LMR/CL-LMT
have five comparison modes.
Caution!
Analog signals are more sensitive to interference than
digital signals.Consequently, greater care must be taken
when laying and connecting the signal lines.
Set the switching hysteresis to a value so that interference
signals will not cause accidental switching. A value of 0.2
V (value 20 without gain) must be observed as a safety
value.
Function of the Less than comparison
Parameter display and parameter set for Less than analog
+
value comparator.
Æ
æ
Circuit diagram with analog value comparator.
F1 +0
h
The values
A gain is not used with any values. No offset is used.
Analog value comparator/
threshold value switch
F2 +0
OS +0
,
and
were not defined.
103