1SVC 440 795 M0100
Oscillations (IEC 60068-2-6)
Shock (IEC 60068-2-27)
Drop (IEC 60068-2-31)
Free fall, when packed (IEC 60068-2-32)
Electromagnetic compatibility (EMC)
Electrostatic discharge (ESD), (IEC/EN 61 000-4-2,
severity level 3)
Electromagnetic fields (RFI), (IEC/EN 61000-4-3)
Emitted interference Interference immunity
(EN 55011, EN 55022) IEC 61000-6-1,2,3,4
Fast transient burst (IEC/EN 61000-4-4,
severity level 3)
High-energy pulses (surge) CL-AC
(IEC/EN 61000-4-5)
High-energy pulses (surge) CL-DC1, CL-DC2,
CL-AC1 (IEC/EN 61000-4-5, severity level 2)
Immunity to line-conducted interference to
(IEC/EN 61000-4-6)
Insulation resistance
Clearance and creepage distances
Insulation resistance
Overvoltage category/degree of pollution
Tools and cable cross-sections
solid core
Flexible with ferrule
Slot-head screwdriver, width
Tightening torque
Technical data
10 to 57 Hz (constant amplitude 0.15 mm)
57 to 150 Hz (constant acceleration 2 g)
18 shocks (semi-sinusoidal 15 g/11 ms)
Drop height 50 mm
1 m
8 kV air discharge,
6 kV contact discharge
Field strength 10 V/m
Class B
2 kV power cables,
2 kV signal cables
2 kV power cable symmetrical
0.5 kV power cable symmetrical
10 V
EN 50178, UL 508, CSA C22.2, No 142
EN 50178
II/2
min. 0.2 mm2, max. 4 mm2/AWG:22 – 12
2
min. 0.2 mm
, max. 2.5 mm
AWG: 22 – 12
Factory wiring: to AWG 30
3.5 x 0.8 mm
0.6 Nm
2
/
255