I.L. 40-385.1B
1. FT-14 TEST PLUG
Right-Side
Left-Side
2. TEST FIXTURE AND EXTENDER BOARD
Inner Chassis Test Fixture (5 Amp)
Inner Chassis Test Fixture (1 Amp)
External Board Assembly
TABLE 3-3. SINGLE-POLE-TRIP OPERATING MODES
"TTYP"
SET AT
POSITION
OFF
1PR
2PR
3PR
SPR
SR3R
3-34
TABLE 3-2. MDAR ACCESSORIES
1355D32G01
1355D32G02
2409F39G01
2409F39G02
1609C55G01
TRIP MODE
3PT on all faults
3PT on all faults
3PT on all faults
3PT on all faults
SPT on φG faults
3PT on others
SPT on φG faults
3PT on others
RECLOSING INITIATE
No reclosing
RI2 on φG faults only
RI2 on φG/φφ/φφG faults
RI2 on all faults
RI1 on φG faults only
no reclosing on others
RI1 on φG faults
RI2 on others