1SVC 440 795 M0100

Terminals

Connecting the power
supply
Open the CL-LINK connections on the side of both CL
X
devices.
Fit the CL-LINK data plug CL-LAS.TK011 in the opening
X
provided on the expansion device.
Plug the devices together.
X
Proceed in the reverse order to dismantle the device.
X

Tools

Slot-head screwdriver, width 3.5 mm, tightening torque
0.6 Nm.

Cable cross-sections

• Solid: 0.2 to 4 mm
• Flexible with ferrule: 0.2 to 2.5 mm2
h
The required connection data for device types CL-AC1
with the voltage 24 V AC, CL-AC2 with the standard
voltage of 100 V to 240 V AC, CL-DC1 with the voltage
12 V DC and CL-DC2 with 24 V DC is provided in section
"Technical data", Page 254.
The CL-LSR/CL-LST and CL-LMR/CL-LMT logic relays
perform a two-second system test after the power supply
voltage is applied. Either RUN or STOP mode will be
activated after these two seconds, depending on the
default setting.

Cable protection

The logic relay requires cable protection (F1) rated for at
least 1 A (slow).