Timing Relay Modes - ABB CL Series Applications Manual

Logic relays
Hide thumbs Also See for CL Series:
Table of Contents

Advertisement

1SVC 440 795 M0100
Parameters
X
?X
â
â
?
â
X
â
?X
ü
Ü
Ü
Parameters
S
00.000
M:S 00:00
H:M 00:00

Timing relay modes

Switch function
Switch with on-delay
Switch with on-delay and random time range
Switch with off-delay
Switch with off-delay and random time range
On- and off-delayed, two time setpoints
On- and off-delayed switching with random time, 2 time setpoints
Single-pulse switching
Flash switching, mark-to-space ratio = 1:1, 2 time setpoints
Flash switching, mark-to-space ratio k 1:1, 2 time setpoints
Time range
Time range and setpoint time
Seconds: 0.00 to 99.99 s
Minutes: Seconds 00:00 to 99:59
Hours: Minutes, 00:00 to 99:59
h
Minimum time setting:
If a time value is less than the logic relay's cycle time, the
elapsed time will not be recognised until the next cycle.
This may cause unforeseeable switching states.
Variable values as time setpoint (I7, I8, I11, I12, actual value
T1 to T16, C1 to C16)
h
If the value of the variable is greater than the maximum
permissible value of the configured time range, the
maximum value of the time range will be used as the
setpoint.
Timing relays
Resolution
10 ms
1 s
1 min.
151