ABB CL Series Applications Manual page 272

Logic relays
Hide thumbs Also See for CL Series:
Table of Contents

Advertisement

1SVC 440 795 M0100
T
= 1 ms
Utilization factor
0.95
R = 48 O
Relative duty factor
L = 16 mH
Maximum switching frequency f = 0.5 Hz
Maximum duty factor DF = 50 %
DC13
Utilization factor
T
= 72 ms
0.95
Relative duty factor
R = 48 O
Maximum switching frequency f = 0.5 Hz
L = 1.15 H
Maximum duty factor DF = 50 %
Other inductive loads:
T
= 15 ms
Utilization factor
0.95
R = 48 O
Relative duty factor
L = 0.24 H
Maximum switching frequency f = 0.5 Hz
Maximum duty factor DF = 50 %
Inductive loading with external suppressor circuit for each load
(a section "Connecting transistor outputs", Page 51)
Utilization factor
Relative duty factor
max. operating frequency
Max. duty factor
Technical data
g = 0.25
%
100
Operations/h
1500
g = 0.25
%
100
Operations/h
1500
g = 0.25
%
100
Operations/h
1500
g = 1
%
100
Operations/h
Depending on
the suppressor
circuit
269

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cl-lsr 12ac2 seriesCl-lsr 12dc2 seriesCl-lst 12dc2 seriesCl-lsr 12ac1 seriesCl-lmr 18ac1 seriesCl-lmr 18ac2 series ... Show all

Table of Contents