TP48200A-DT19D1 Telecom Power
User Manual
Item
Cabling
A.5 Direct Ventilation Specifications
Table A-5 Direct ventilation specifications
Item
Heat exchanging capacity
Input voltage
Operating temperature
Storage temperature
Altitude
Noise
A.6 Heater Specifications
Table A-6 Heater specifications
Item
Input voltage
Voltage frequency
Operating temperature
Heater start and stop temperature
Operating humidity
Heating power
A.7 TEC04C Specifications
Table A-7 TEC04C specifications
Item
Rated voltage
Rated cooling capacity (L32/L32)
Issue 03 (2019-11-15)
Specifications
220 V AC single-phase or 110 V AC dual-live wire
Rated frequency: 50 Hz or 60 Hz
-40° C to +65° C (-40° F to +149° F)
The heater starts when the temperature is 0° C and stops when the
temperature is 15° C.
5% RH to 95% RH
> 500 W
Specifications
-48 V DC
200 W
Copyright © Huawei Technologies Co., Ltd.
Specifications
Routed in and out from the bottom
Specifications
2000 W (200 W/K, 10° C temperature difference)
-48 V DC
-10° C to +45° C with 1120W/m
-40° C to +70° C
< 4000 m
< 65 dB (A)
A Technical Specifications
2
solar radiation
86