Huawei TP48200A-DT19D1 Telecom Power User Manual page 91

Table of Contents

Advertisement

TP48200A-DT19D1 Telecom Power
User Manual
Item
Specifications
THD
DC output
Output voltage range
Default output voltage
Output power
Regulated voltage precision
Ripple and noise
Psophometrically weighted noise
Current imbalance
AC input
AC input overvoltage protection threshold
protection
AC input overvoltage recovery threshold
AC input undervoltage protection threshold
AC input undervoltage recovery threshold
DC output
DC output overvoltage protection threshold
protection
AC surge
Nominal lightning strike discharge current: 20 kA (8/20 µ s); maximum lightning strike
protection
discharge current: 40 kA (8/20 µs)
DC surge
Differential mode: 10 kA (8/20 µs); common mode: 20 kA (8/20 µs)
protection
Safety and
IEC/EN60950-1 and IEC/EN60950-22
regulatory design
Mean time
200,000 hours (30° C)
between failures
(MTBF)
Issue 03 (2019-11-15)
Copyright © Huawei Technologies Co., Ltd.
A Technical Specifications
≤ 5% (load percentage ≥ 50%)
–42 V DC to –58 V DC
–53.5 V DC
Maximum output power = Output power of
a single rectifier x Number of rectifiers
≤ ±1%
≤ 200 mVp-p
≤ 2 mV
< ± 5% (20%–100% load)
> 300 V AC
When the voltage is restored to 290 V AC,
the output resumes.
< 85 V AC
When the voltage is restored to 90 V AC,
the output resumes.
–58.5 V DC to –60.5 V DC
1. If overvoltage occurs due to an internal
fault, the rectifier locks out.
2. If the external voltage is greater than
–63 V for more than 500 ms, the
rectifier locks out.