Emc Specifications; Cabinet Specifications - Huawei TP48200A-DT19D1 Telecom Power User Manual

Table of Contents

Advertisement

TP48200A-DT19D1 Telecom Power
User Manual
A.3 EMC Specifications
Table A-3 EMC specifications
Item
Electromagnetic
interference (EMI)
Electromagnetic
susceptibility (EMS)
A.4 Cabinet Specifications
Table A-4 Cabinet specifications
Item
Cabinet dimensions (H x W x D)
Cabinet weight (excluding rectifiers and batteries)
Protection level
Installation mode
Maintenance mode
Issue 03 (2019-11-15)
Specifications
Conducted emission (CE)
Radiated emission (RE)
Harmonic current
Voltage fluctuation and flick
Electrostatic discharge (ESD)
Electrical fast transient (EFT)
Radiated susceptibility (RS)
Conducted susceptibility (CS)
Surge immunity
Voltage dips immunity (DIP)
Copyright © Huawei Technologies Co., Ltd.
Class A, EN300386
Class A, EN300386
IEC61000-3-12
IEC61000-3-11
IEC61000-4-2 (criterion B)
Contact discharge: 6 kV; air discharge: 8 kV
IEC61000-4-4 (criterion B)
AC power port: ± 2 kV; DC power port: ± 1 kV;
signal port: ± 1 kV
IEC61000-4-3 (criterion A)
10 V/m
IEC6100-4-6 (criterion A)
Power port: 10 V; signal port: 3 V
IEC61000-4-5 (criterion B)
AC power port: differential mode: ± 2 kV (8/20
µs); common mode: ± 4 kV (8/20 µs)
DC power port: differential mode: ± 2 kV (8/20
µs); common mode: ± 4 kV (8/20 µs)
Signal port: differential mode: 0.5 kV (8/20 µs);
common mode: 1 kV (8/20 µ s)
IEC61000-4-11
Specifications
2030 mm x 820 mm x 760 mm (including the base)
< 200 kg
IP55
Installed on a floor or against a wall
Operated and maintained from the front
A Technical Specifications