TP48200A-DT19D1 Telecom Power
User Manual
Figure 4-5 Replacing an AC SPD module
Step 4 Disconnect the ground cable of the ESD wrist strap, and remove the ESD wrist strap and ESD
gloves.
----End
Follow-up Procedure
Check that the alarm for the AC SPD is cleared.
4.4.4 Replacing a Circuit Breaker
Prerequisites
Before replacing an AC circuit breaker, switch off the upstream input circuit breaker.
Procedure
Step 1 Unscrew and remove the cover of the circuit breaker.
Step 2 Switch off the circuit breaker.
Step 3 Record the positions where the cables and signal cable terminals connect to the circuit
breaker.
Step 4 Loosen the screw that secures the upper port of the circuit breaker using a Phillips screwdriver,
and remove the power cable and signal cable terminals. Wrap the cable and terminals using
insulation tape.
Issue 03 (2019-11-15)
The cabinet door key, insulation tape, and required tools are available.
The new circuit breaker is intact and has the same specifications as the circuit breaker to
be replaced.
Copyright © Huawei Technologies Co., Ltd.
4 Maintenance
58
Need help?
Do you have a question about the TP48200A-DT19D1 Telecom Power and is the answer not in the manual?
Questions and answers