Huawei TP48200A-DT19D1 Telecom Power User Manual page 29

Table of Contents

Advertisement

TP48200A-DT19D1 Telecom Power
User Manual
Figure 3-3 Rectifier
(1) Run indicator
(4) Locking latch
Table 3-1 Rectifier indicator description
Indicator
Color
Run
Green
indicator
Alarm
Yellow
indicator
Fault
Red
indicator
Issue 03 (2019-11-15)
Status
Description
Steady on
The rectifier has an AC power input.
Off
The rectifier has no AC power input.
The rectifier is faulty.
Blinking at 0.5 Hz
The rectifier is being queried.
Blinking at 4 Hz
The rectifier is loading an application program.
Off
No alarm has been generated.
Steady on
The rectifier is protecting itself against AC input overvoltage
or undervoltage.
The rectifier is hibernating.
Blinking at 0.5 Hz
The communication between the rectifier and the SMU has
been interrupted.
Off
The rectifier is running properly.
Steady on
The rectifier has been locked out due to output overvoltage.
The rectifier has no output due to an internal fault.
Copyright © Huawei Technologies Co., Ltd.
(2) Alarm indicator
(5) Handle
The rectifier has generated an alarm due to ambient
overtemperature.
The rectifier has generated an alarm for shutdown due to
ambient overtemperature or undertemperature.
3 Components
(3) Fault indicator
22